版權說明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權,請進行舉報或認領
文檔簡介
ICS91.060.30
河北省工程建設標準
P32T/HBZxxx一2023
裝配式3D地暖模塊應用技術標準
technicalstandardforapplicationofprefabricated3Dfloor
radiantheatingmodule
2023-xx-xx發(fā)布2023-xx-xx實施
河北省墻材革新和建筑節(jié)能協(xié)會發(fā)布
目次
1總則·········································································1
2術語·········································································2
3基本規(guī)定··································································4
4性能要求··································································6
4.1主要材料································································6
4.2配套材料·······························································11
5設計·······································································13
5.1一般規(guī)定······························································13
5.2設計要點······························································14
6施工·······································································16
6.1一般規(guī)定······························································16
6.2施工要點······························································17
6.3成品保護······························································19
6.4加熱管安裝及面層施工···············································20
7質(zhì)量驗收·································································22
7.1一般規(guī)定······························································22
7.2主控項目······························································24
7.3一般項目······························································26
附錄A抗沖擊性能試驗方法·············································28
本標準用詞說明····························································30
引用標準名錄·······························································31
附:條文說明·······························································33
1總則
1.0.1為規(guī)范裝配式3D地暖模塊在建筑地面輻射供暖系統(tǒng)工程
中的應用,做到安全適用、技術先進,保證工程質(zhì)量,制定本標
準。
1.0.2本標準適用于河北省新建、改建或擴建民用建筑地面輻射
供暖系統(tǒng)采用裝配式3D地暖模塊的設計、施工及質(zhì)量驗收。
1.0.3裝配式3D地暖模塊的設計、施工和驗收,除應符合本標準
的規(guī)定外,尚應符合國家、行業(yè)和河北省現(xiàn)行有關標準的規(guī)定。
1
2術語
2.0.1地面輻射供暖floorradiantheating
提升地表溫度,形成熱輻射面,通過輻射面以輻射和對流的
傳熱方式向室內(nèi)供暖。
2.0.2裝配式3D地暖模塊prefabricated3Dfloorradiantheating
module
以保溫層(石墨擠塑板、擠塑聚苯板)或以帶有隔聲增強層
的保溫層為保溫隔聲層,以帶有固定間距、尺寸的預制溝槽3D無
機板為支撐,及按需設置的均熱構造層復合而成的,用在建筑地
面輻射供暖系統(tǒng)中現(xiàn)場拼裝并敷設加熱管的專用板塊。
裝配式3D地暖模塊按建筑地面保溫隔聲系統(tǒng)樓板計權標準
化撞擊聲壓級分為:Ⅰ型裝配式3D地暖模塊、Ⅱ型裝配式3D地
暖模塊。
2.0.3裝配式3D地暖模塊系統(tǒng)prefabricated3Dfloorradiant
heatingmodulesystem
置于建筑物地面結構層上,由粘結層、裝配式3D地暖模塊及
豎向隔聲片等構成的建筑地面保溫隔聲構造。
2.0.4擠塑聚苯乙烯泡沫板(以下簡稱擠塑板)extruded
polystyrenefoamboard
以聚苯乙烯樹脂或其共聚物為主要成分,可添加石墨及其他
添加劑,經(jīng)擠塑發(fā)泡成型的具有閉孔結構的硬質(zhì)塑料板狀制品。
2.0.5預制溝槽3D無機板prefabricatedgroove3Dinorganic
plate
預制溝槽3D無機板由普通硅酸鹽水泥、建筑石膏、聚丙烯纖
維、耐堿玻纖網(wǎng)格布等組成,用于敷設加熱部件且具有吸聲、抗
2
壓、抗沖擊作用的立體加固增強結構,位于保溫板上表面及側(cè)面。
2.0.6隔聲增強層soundinsulationenhancementlayer
具有較好減震、吸聲性能的板狀或卷狀材料,如橡膠墊、聚
酯纖維等。
2.0.7均熱構造層heatdistributionplates
采用裝配式3D地暖模塊的供暖地面,鋪設在加熱部件上、下
的可使加熱管產(chǎn)生的熱量均勻散開的金屬材料層。毛坯交房的項
目應對裸露的地暖輻射管線、鋁箔等,采用防水、阻燃聚酯氈覆
蓋,做好成品保護。
2.0.8水泥基膠粘劑cement-basedadhesive
由水硬性膠凝材料、集料、添加劑等組成的粉狀混合物,使
用時需與水或其它液體混合物拌和,在裝配式3D地暖模塊鋪設中
局部使用,起調(diào)平固定作用。
2.0.9豎向隔聲片verticalsoundinsulationfilm
設置在保溫隔聲輻射地暖模塊與四周墻體、柱及穿樓管道之
間的彈性片材,以阻斷樓面與墻體、柱及穿樓管道之間的聲橋。
2.0.10填充板fillerplate
裝配式3D地暖模塊系統(tǒng)中,與單體工程選用的裝配式3D地
暖模塊材質(zhì)、構造和總厚度相同,用于填充房間內(nèi)未鋪設供暖管
線的部位。
2.0.11架空板fillerplate
裝配式3D地暖模塊系統(tǒng)中,與單體工程選用的裝配式3D地
暖模塊材質(zhì)、總厚度相同,一字型及L型支撐形成架空層。下部
可敷設給水管線及電氣強弱電管線。
2.0.12干式工法non-wetconstruction
現(xiàn)場采用干作業(yè)施工工藝的建造方法。
3
3基本規(guī)定
3.0.1采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng),其各項指
標應符合《民用建筑熱工設計規(guī)范》GB50176、《民用建筑隔
聲設計規(guī)范》GB50118、《建筑環(huán)境通用規(guī)范》GB55016、《建
筑節(jié)能與可再生能源利用通用規(guī)范》GB55015等現(xiàn)行國家、行業(yè)
及地方有關標準的規(guī)定和設計要求。
3.0.2采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)所使用的材
料,應根據(jù)系統(tǒng)工作溫度、系統(tǒng)工作壓力、建筑荷載、建筑設計
壽命、現(xiàn)場防水、防火以及施工性能等要求,經(jīng)綜合比較后確定,
其材料均應符合國家現(xiàn)行相關標準的規(guī)定。
3.0.3裝配式3D地暖模塊系統(tǒng)組成材料應配套使用。地暖模塊
施工驗收完畢,應對表面進行覆蓋保護;后續(xù)工序施工時,應嚴
格按照操作流程施工,保護地暖模塊不受損壞。
3.0.4裝配式3D地暖模塊施工前,應進行地暖模塊排布設計。
地暖模塊宜優(yōu)先選用標準模塊,當標準模塊尺寸不滿足房間尺寸
時,可采用非標準尺寸模塊;需在排布設計圖紙中標注或說明非
標準尺寸模塊的尺寸。
3.0.5采用裝配式3D地暖模塊進行地面輻射供暖系統(tǒng)設計時,
應注明具體的供回水溫度。供回水溫度應由計算確定,且應根據(jù)
供回水溫度標明裝配式3D地暖模塊的向上有效散熱量和向下散
熱損失,并校核向上散熱量是否滿足室內(nèi)熱負荷要求。
3.0.6采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)的供暖運行
調(diào)試,應在正常供暖條件下進行。
4
3.0.7采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)未經(jīng)供暖調(diào)
試,不得運行使用。
3.0.8裝配式3D地暖模塊系統(tǒng)應確保施工質(zhì)量符合相關標準規(guī)
定及設計要求。
5
4性能要求
4.1主要材料
4.1.1裝配式3D地暖模塊按照模塊上表面溝槽形式分為直
線溝槽型和曲線溝槽型;地暖模塊的曲線溝槽彎曲半徑應滿
足8倍加熱管外徑的要求。裝配式3D地暖模塊按照隔聲性能
分為Ⅰ型裝配式3D地暖模塊、Ⅱ型裝配式3D地暖模塊,基本構
造見圖4.1.1-1、4.1.1-2。
a-均熱構造層(薄鋁板或鋁箔,上方敷設加熱管),b-預制溝槽3D無機板,
c-保溫隔聲層(厚度及材質(zhì)見單體設計)
圖4.1.1-1Ⅰ型裝配式3D地暖模塊基本構造
a-均熱構造層(薄鋁板或鋁箔,上方敷設加熱管),b-預制溝槽3D無機板
c-保溫隔聲層(厚度及材質(zhì)見單體設計),d-隔聲增強層(厚度及材質(zhì)見單體設計)
圖4.1.1-2Ⅱ型裝配式3D地暖模塊基本構造
6
4.1.2架空板構造見圖4.1.2。
a-預制溝槽3D無機板,b-保溫隔聲層(厚度及材質(zhì)見單體設計)
圖4.1.2架空板基本構造
4.1.3預制溝槽3D無機板基本構造見圖4.1.3。
圖4.1.3預制溝槽3D無機板基本構造
4.1.4裝配式3D地暖模塊的性能指標應符合表4.1.4的規(guī)定。
表4.1.4裝配式3D地暖模塊性能指標
項目單位性能指標試驗方法
單位面積質(zhì)量kg/㎡≤38JG/T287
抗壓強度MPa≥1.25GB/T5486
GB/T10294
保溫層導熱系數(shù)W/(m·K)≤0.030
GB/T10295
體積吸水率%≤8.0GB/T5486
IRa—≤1.0
放射性GB6566
Ir—≤1.0
燃燒性能等級—B1級GB8624
7
續(xù)表4.1.4
甲醛釋放量mg/m3≤0.12GB50325
抗沖擊性能—無破碎開裂或脫落附錄A
注:表中甲醛釋放量指標為包含保溫層和均熱構造層的性能指標;其他指標檢測時去
除均熱構造層;檢測抗壓強度取樣時,檢測試塊應包含有50mm*50mm的3D支撐構造。
4.1.5鋪設裝配式3D地暖模塊系統(tǒng)的樓板,其隔聲性能指標應
符合表4.1.5的規(guī)定。
表4.1.5隔聲性能指標
性能指標
項目單位試驗方法
I型II型
計權標準化撞擊聲壓級
dB≤65≤55GB/T19889.7
L'nT,w(現(xiàn)場檢測)
4.1.6裝配式3D地暖模塊主要規(guī)格尺寸及尺寸允許偏差、外觀
質(zhì)量應符合表4.1.6-1、4.1.6-2的規(guī)定。
表4.1.6-1裝配式3D地暖模塊主要規(guī)格尺寸(mm)
項目規(guī)格尺寸
長度600
寬度400
管槽軸線間距200
管槽深度20
管槽寬度20
整體厚度45
預制溝槽無機板上表面厚度
3D23
預制溝槽無機板側(cè)面厚度
3D10
保溫板厚度≥20
8
表4.1.6-2裝配式3D地暖模塊尺寸允許偏差(mm)
項目允許偏差(mm)試驗方法
長度±2.0GB/T5486
寬度±2.0GB/T5486
厚度±2.0GB/T5486
管槽軸線間距±2.0游標卡尺
管槽深度±1.0游標卡尺
溝槽寬度±1.0游標卡尺
保溫板厚度+2.0GB/T6342
預制溝槽無機板上表面厚度
3D+2.0游標卡尺
預制溝槽3D無機板側(cè)面厚度±2.0游標卡尺
對角線差±3.0GB/T5486
板面平整度≤2.0GB50209
裂紋寬度≤0.2GB/T50152
缺棱掉角≤20游標卡尺
4.1.7裝配式3D地暖模塊載荷性能指標應符合表4.1.7的規(guī)定。
表4.1.7裝配式3D地暖模塊載荷性能指標
項目單位性能指標試驗方法
極限集中
荷載值N1600
荷載
GB/T36340
沖擊點的塌陷值不大于
耐沖擊性能-
1.5mm。模塊不能有破裂塌陷
4.1.8預制溝槽3D無機板性能指標性能指標應符合表4.1.8的
規(guī)定。
9
表4.1.8預制溝槽3D無機板性能指標
項目單位性能指標試驗方法
干密度kg/m31100~1800GB/T5486
抗壓強度MPa≥5JGJ/T70
4.1.9保溫隔聲層的保溫板可選用石墨擠塑板或擠塑聚苯板,保
溫板的性能指標應符合表4.1.9的規(guī)定。
表4.1.9保溫板性能指標
性能指標
項目試驗方法
石墨擠塑板擠塑聚苯板
表觀密度kg/m322~3522~35
導熱系數(shù)[W/(m·K)]≤0.024≤0.030
垂直板面的抗拉強度(MPa)≥0.20
壓縮強度(MPa)≥0.20GB/T10801.2
尺寸穩(wěn)定性[(70±2)°C,48h](%)≤1.5GB/T30595
彎曲變形(mm)≥20
水蒸氣透濕性能[ng/(Pa·m·s)]1.5~3.5
吸水率(%)≤1.5
燃燒性能B1級GB/T8624
注:擠塑板在工程應用前,應在自然條件下陳化不少于28天;擠塑板產(chǎn)品不得摻加非
本廠擠塑板產(chǎn)品的回收料,在出廠前應雙面去皮。
4.1.10裝配式3D地暖模塊及其均熱構造層的溝槽尺寸應與敷
設的加熱部件外徑吻合,且應符合下列規(guī)定:
1裝配式3D地暖模塊總厚度不應小于表4.1.6-1的要求;
2均熱構造層材料采用導熱系數(shù)不小于237W/(m·K)的薄
鋁板或鋁箔,均熱構造層最小厚度宜滿足表4.1.10的要求。
10
表4.1.10均熱構造層材料最小厚度(mm)
木地板面層
類別地磚類面層
管間距<200管間距≥200
單層雙層單層雙層
加熱管—0.20.10.40.2
注:1地磚類面層指在敷設有加熱管的裝配式3D地暖模塊上直接粘貼地磚、石材
的做法,木地板面層指在敷設有加熱管的裝配式3D地暖模塊上直接敷設木地板的做法;
2單層均熱構造層,指僅采用帶金屬均熱構造層的裝配式3D地暖模塊,加熱
管上不再鋪設均熱構造層時的最小厚度;雙層均熱構造層,指在采用帶金屬均熱構造層
的裝配式3D地暖模塊的基礎上,在加熱管上再鋪設一層金屬均熱構造層時每層的最小
厚度。
4.1.11裝配式3D地暖模塊填充板、架空板材料性能同地暖模
塊。
4.1.12裝配式3D地暖模塊預制溝槽間距和尺寸設置應符合現(xiàn)
行行業(yè)標準《輻射供暖供冷技術標準》JGJ142的規(guī)定。
4.2配套材料
4.2.1裝配式3D地暖模塊采用的水泥基膠粘劑除應符合現(xiàn)行行
業(yè)標準《預拌砂漿應用技術規(guī)程》JGJ/T223的有關規(guī)定外,其性
能指標尚應符合表4.2.1的要求。
表4.2.1水泥基膠粘劑性能指標
項目單位性能指標試驗方法
標準狀態(tài)≥0.50
浸水后≥0.50
拉伸粘結強度JC/T547
MPa
熱老化后≥0.50
11
續(xù)表4.2.1
凍融循環(huán)后≥0.50
晾置時間≥20min≥0.50
可操作時間h1.5~4.0JC/T547
4.2.2水泥基膠粘劑應符合現(xiàn)行行業(yè)標準《陶瓷磚膠粘劑》JC/T
547的有關規(guī)定。
4.2.3裝配式3D地暖模塊及采用的系統(tǒng)材料應符合現(xiàn)行國家標
準《建筑材料放射性核素限量》GB6566。
4.2.4豎向隔聲片宜采用橡膠隔聲墊、聚酯纖維復合卷材、難燃
型改性聚乙烯復合卷材等具有保溫隔聲一體化功能的材料,其性
能應符合現(xiàn)行國家、行業(yè)和地方有關標準的規(guī)定。
4.2.5Ⅱ型裝配式3D地暖模塊中的隔聲增強層宜采用橡膠隔聲
墊、聚酯纖維復合卷材、難燃型改性聚乙烯復合卷材等具有隔聲
功能的材料,其性能應符合現(xiàn)行國家、行業(yè)和地方有關標準的規(guī)
定。
4.2.6裝配式3D地暖模塊采用的均熱構造層、加熱供冷管、輸
配管、分水器、集水器、閥門、附件、溫控及計量設備等應符合
現(xiàn)行行業(yè)標準《輻射供暖供冷技術標準》JGJ142的規(guī)定。
12
5設計
5.1一般規(guī)定
5.1.1裝配式3D地暖模塊系統(tǒng)的構造做法應符合現(xiàn)行國家標準
《建筑地面設計規(guī)范》GB50037、《民用建筑供暖通風與空氣
調(diào)節(jié)設計規(guī)范》GB50736、《建筑節(jié)能與可再生能源利用通用
規(guī)范》GB55015、《建筑環(huán)境通用規(guī)范》GB55016和現(xiàn)行行業(yè)
標準《輻射供暖供冷技術規(guī)程》JGJ142的有關規(guī)定。
5.1.2Ⅱ型裝配式3D地暖模塊系統(tǒng)的隔聲設計應符合現(xiàn)行國家
標準《民用建筑隔聲設計規(guī)范》GB50118和《建筑環(huán)境通用規(guī)
范》GB55016的有關規(guī)定。
5.1.3裝配式3D地暖模塊中的保溫板的厚度應根據(jù)熱工設計確
定,且最小設計厚度不應小于20mm。
5.1.4采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng),房間內(nèi)的
生活給水等其他水管,以及敷設在地面內(nèi)的其他電氣系統(tǒng)管線,
不應與地面供暖散熱部件在同一溝槽內(nèi)。
5.1.5裝配式3D地暖模塊輻射表面向上的供熱量或供暖量,以
及向下的傳熱量應按產(chǎn)品檢測數(shù)據(jù)確定。
5.1.6裝配式3D地暖模塊安裝完成后,可在其上部直接鋪貼地
磚、石材或鋪設木地板面層。
5.1.7采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)供、回水溫
度應由計算確定,供水溫度不應大于60°C,供回水溫差不宜大于
10°C且不宜小于5°C。民用建筑供水溫度宜采用35°C~45°C。
13
5.2設計要點
5.2.1應按實際計算所得的室內(nèi)計算熱負荷值確定溝槽間
距。
5.2.2當?shù)孛婧奢d大于裝配式3D地暖模塊供暖地面的承載能
力時,應進行設計復核。
5.2.3裝配式3D地暖模塊排布設計圖,除應標注地暖模塊類
型、尺寸等信息外,尚應注明地暖模塊的鋪裝順序。
5.2.4采用架空板進行水管、弱電等管線分離設計時,應注
明地暖模塊總高度及架空層高度,并繪制架空層內(nèi)管線綜合
設計圖紙,且對敷設在架空層內(nèi)的管線進行準確定位。
5.2.5分水器、集水器與加熱區(qū)域之間的連接管,應敷設在
定制的裝配式3D地暖模塊中;地暖管密集部位,當主規(guī)格標
準尺寸地暖模塊不滿足設計要求時,可采用定制化非標地暖
模塊;排布設計圖應標明定制非標地暖模塊的尺寸相關參
數(shù)。
5.2.6建筑樓層地面與柱、墻面交界處應粘貼豎向隔聲片,
鋪設的高度應超出裝配式3D地暖模塊上表面20mm或裝飾面
層,且應收口于踢腳線內(nèi),地面有豎向管道時,豎向隔聲片
應包裹管道四周,鋪設的高度與柱、墻面的鋪設高度一致。
5.2.7地面輻射供暖系統(tǒng)宜采用有均熱構造層的裝配式3D地
暖模塊。直接鋪設木地板面層時應采用有均熱構造層的裝配
式3D地暖模塊,且在模塊和加熱管之上宜再鋪設一層均熱構造
層。
5.2.8采用裝配式3D地暖模塊時,與供暖房間相鄰的樓板,
14
可不設置絕熱層。直接與室外空氣接觸的樓板或與不供暖房
間相鄰的地板作為供暖輻射地面時,必須設置絕熱層。其他部位
絕熱層的設置應符合《輻射供暖供冷技術規(guī)程》JGJ142的規(guī)定。
5.2.9門洞口處裝配式3D地暖模塊應鋪設至采暖空間墻體外側(cè)
邊緣處,并做好防水防潮處理。
5.2.10廁浴間、廚房等有防水要求的房間采用裝配式3D地
暖模塊建筑地面系統(tǒng)時,系統(tǒng)面層下應設防水隔離層,樓板
四周除門洞口外應采用強度等級不低于C20的混凝土進行翻
邊,其高度不小于200mm。
15
6施工
6.1一般規(guī)定
6.1.1采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)施工
前,施工單位應建立有效的工程質(zhì)量管理體系、施工質(zhì)量控
制和檢驗制度,編制專項工程施工方案,并經(jīng)監(jiān)理(建設)
單位審查批準。裝配式3D地暖模塊的施工,除滿足本標準
規(guī)定外,尚應滿足國家現(xiàn)行標準中對地面輻射供暖系統(tǒng)的相
關規(guī)定。
6.1.2方案實施前應對施工作業(yè)人員進行現(xiàn)場技術安全交
底和必要的實際操作培訓。
6.1.3設計單位應具有相應的設計資質(zhì),裝配式3D地暖模
塊的地面輻射供暖系統(tǒng)應按照審查合格的設計文件和經(jīng)審
查批準的專項施工方案施工,在施工過程中不得隨意更改專
項設計。深化設計或修改應有設計單位出具的設計變更文
件,或經(jīng)原設計單位確認后方可施工。
6.1.4裝配式3D地暖模塊所采用的材料應有產(chǎn)品合格證書
和性能檢測報告,材料的品種、規(guī)格、性能等應符合設計和
產(chǎn)品標準的要求。材料進場后,應按規(guī)定抽樣復驗,并經(jīng)監(jiān)
理工程師核查確認。復驗不合格的嚴禁在工程上使用。
6.1.5管材、管件進場應由供暖工程的施工單位對管材壁厚
等外觀指標進行現(xiàn)場復試檢驗。
6.1.6大面積施工前,應在現(xiàn)場采用相同材料、構造做法和
工藝制作樣板,并經(jīng)建設相關各方確認后方可進行后期施
16
工。
6.1.7施工安裝前應具有下列條件:
1施工組織設計或施工方案應已批準,采用的技術標
準和質(zhì)量控制措施文件應齊全并已完成交底;
2材料進場抽檢已合格并滿足安裝要求;
3施工現(xiàn)場應具有供水、供電條件,應有儲存材料的
臨時設施;
4土建專業(yè)應已完成墻面抹灰(不含面層),外窗、
外門應已安裝完畢,地面應已清理干凈,衛(wèi)生間應做完閉水
試驗并應經(jīng)過驗收;
5相關電氣預埋等工程應已完成;
6.1.8每道工序完成后,應經(jīng)監(jiān)理(建設)單位檢查驗收合
格后方可進行下道工序的施工。當下道工序或相鄰工程施工
時,應對已完成的部分采取保護措施。
6.1.9裝配式3D地暖模塊施工期間以及施工完成24小時
內(nèi),基層及環(huán)境溫度不應低于5℃。在低于0°C的環(huán)境施
工時,現(xiàn)場應采取升溫措施,但不得采用明火。
6.2施工要點
6.2.1施工時不宜與其他工種交叉施工作業(yè),所有地面留
洞、伸出地面的管道、設備、基座或預埋件等應在地暖模塊
鋪設施工前完成,并做好密封防水處理。
6.2.2裝配式3D地暖模塊底層地面施工應待防水防潮層施
工完成后再按樓層地面的施工流程進行施工。
17
6.2.3底層地面的墊層、調(diào)平固定層、防水層尚應符合《建
筑地面設計規(guī)范》GB50037、《建筑地面工程施工質(zhì)量驗收
規(guī)范》GB50209、《建筑裝飾裝修工程質(zhì)量驗收標準》GB50210
的規(guī)定。
6.2.4各類機具、工具應齊備、安全、可靠,并經(jīng)檢驗合格。
6.2.5裝配式3D地暖模塊施工工序應按以下流程進行:基
層找平處理→彈控制線→鋪貼電子交聯(lián)聚乙烯減震墊→粘
貼豎向隔聲片→干鋪裝配式3D地暖模塊模塊→清潔。
6.2.6施工過程中應嚴格按照施工工藝流程,合理安排各工
序,保證各工序間的銜接和間隔時間,以確保施工質(zhì)量。
6.2.7基層應堅實平整、無損傷、干燥且無油漬、污垢、灰
塵以及其它雜物,地面平整度允許誤差不應大于3mm,鋪設
裝配式3D地暖模塊用水泥基膠粘劑薄貼固定。
6.2.8在墻腳處墻面粘貼豎向隔聲片。豎向隔聲片應高于裝
配式3D地暖模塊表面,且應不間斷布滿房間內(nèi)所有的墻腳
處墻面。豎向隔聲片拼縫寬度不應大于1mm。
6.2.9鋪設裝配式3D地暖模塊應滿足下列要求:
1鋪設裝配式3D地暖模塊時,先采用專用地坪打磨器
對基層高位處進行打磨找平處理,基層平整度施工驗收,基
層找平處理平整度控制到3mm以內(nèi),地暖模塊大面積采用干
鋪方式,局部位置水泥基膠粘劑找平薄貼地暖模塊。
2地暖模塊采用通縫密貼施工,應按照排布設計要求
的鋪裝順序鋪貼。鋪貼時首先依據(jù)設計圖中主規(guī)格板定位
尺寸放線,由室內(nèi)里側(cè)向外側(cè)依次鋪貼。
3地暖模塊鋪設應平整,模塊間相互結合應緊密,板
18
縫應均勻,板縫寬度不宜大于3mm,應粘結平順。
4地暖模塊相鄰板材上的溝槽應對接,接縫應平順,
接縫高低差應不大于1mm。
5地暖模塊鋪貼完畢24h后,方可進行填充板鋪貼。靠
墻部位填充板鋪貼時,要現(xiàn)場復核填充板尺寸,當與現(xiàn)場尺
寸存在誤差時,可對填充板進行現(xiàn)場裁切。
6.2.10施工過程中,加熱管敷設區(qū)域嚴禁穿鑿、穿孔或進
行射釘作業(yè)。施工人員應對加熱管敷設區(qū)域采取防護措施,
不得在施工過程中對模塊、加熱部件造成損傷。
6.2.11施工過程中應防止油漆、瀝青或其他有機溶劑接觸污
染加熱部位的表面。
6.2.12采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)調(diào)試與
試運行,應在施工完畢且養(yǎng)護期滿后,正式運行前進行。
6.3成品保護
6.3.1裝配式3D地暖模塊和加熱部件的運輸、存儲應符合
下列規(guī)定:
1應進行遮光包裝后運輸,不得裸露散裝;
2運輸、裝卸和搬運時,應小心輕放,不得拋、摔、
滾、拖;
3不得暴曬雨淋,宜存儲在溫度不超過40°C且通風
良好的干凈庫房內(nèi);
4應避免因環(huán)境溫度和物理壓力受到損害,并應遠離
熱源。
19
6.3.2施工結束后應繪制竣工圖,并應準確標注加熱部件敷設
位置及地溫傳感器埋設地點。不得進行打洞、釘鑿、撞擊、
高溫作業(yè)等工作。
6.3.3裝配式3D地暖模塊施工驗收完畢,應對表面進行覆
蓋保護,防止鋪裝面層時造成損壞。
6.3.4保護層宜采用透氣性強的無紡布(丙綸布)、膠合板
等材料。保護層鋪裝需平整嚴密,邊角及接縫應用膠帶固定,
不得翹起移動。
6.3.5通道及房間進出口等踩踏頻繁處應采取加強保護措
施,有效防止對模塊及加熱部件造成損傷。
6.4加熱管安裝及面層施工
6.4.1加熱管敷設前應對照施工圖核對加熱管的選型、直徑、
壁厚符合設計要求;應檢查加熱管外觀質(zhì)量和管內(nèi)部無雜
質(zhì),確認后方可施工。
6.4.2加熱管應按照設計圖紙標定的管間距和走向敷設,應
保持平直并完全嵌入溝槽;加熱管安裝完畢或中斷時,敞口
處應隨時封堵。
6.4.3敷設在地面面層下的加熱管不應有接頭。在鋪設過程
中管材出現(xiàn)損壞、滲漏等現(xiàn)象時,應當整根更換,不應拼接
使用。
6.4.4在分水器、集水器附近以及其他局部加熱管排列比較
密集的部位,當管間距小于100mm時,可采用非標定制模塊
或在加熱管外部設置柔性套管等措施。
20
6.4.5按照設計要求未鋪設加熱管的地暖模塊溝槽,應在下
道工序前,采用砂漿或地暖模塊同質(zhì)材料等硬質(zhì)填充物填充
平整、密實。
6.4.6一次分水器、集水器宜在開始鋪設加熱管之前進行安
裝。水平安裝時,宜將分水器安裝在上,集水器安裝在下,
中心距宜為200mm,集水器中心距地面不應小于300mm。
6.4.7面層施工應具備下列條件:
1加熱管水壓試驗合格且處于有壓狀態(tài);
2加熱管驗收合格;
3伸縮縫已預留或設置完畢;
4已通過隱蔽工程驗收。
6.4.8以木地板作為面層時,木材應經(jīng)過干燥處理后,方可
進行地板施工。鋪設施工方法應符合現(xiàn)行行業(yè)標準《地面輻
射供暖木質(zhì)地板鋪設技術和驗收規(guī)范》WB/T1037的有關規(guī)
定。
21
7質(zhì)量驗收
7.1一般規(guī)定
7.1.1檢查、驗收及調(diào)試應由施工單位提出書面報告,監(jiān)理
單位組織各相關專業(yè)進行檢查和驗收,并應做好記錄。
7.1.2專業(yè)施工單位應具有相應的施工資質(zhì),工程質(zhì)量驗收
人員應具備相應的專業(yè)技術資格。
7.1.3采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)施工驗
收應符合《民用建筑隔聲設計規(guī)范》GB50118、《建筑地
面工程施工質(zhì)量驗收規(guī)范》GB50209、《建筑工程施工質(zhì)
量驗收統(tǒng)一標準》GB50300、《建筑節(jié)能工程施工質(zhì)量驗
收規(guī)范》GB50411、《建筑環(huán)境通用規(guī)范》GB55016等現(xiàn)行
相關標準和本標準的規(guī)定。
7.1.4材料和配套輔件(材)必須符合國家、行業(yè)現(xiàn)行標準
要求和設計要求。材料或產(chǎn)品進入施工現(xiàn)場時,應有含中文
標識的出廠質(zhì)量合格證、產(chǎn)品出廠檢驗報告、有效期內(nèi)的系
統(tǒng)型式檢驗報告等。
7.1.5溫控及計量裝置、分水器、集水器及其連接件等安裝
后應有成品保護措施。
7.1.6伸縮縫位置應有固定措施。
7.1.7采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)應在基
層質(zhì)量驗收合格后施工,施工過程中應及時進行質(zhì)量檢查、
隱蔽工程驗收和檢驗批驗收,施工完成后應進行分項工程驗
收。
22
7.1.8裝配式3D地暖模塊鋪設及加熱管安裝完畢后,在找
平層或面層施工前,應按隱蔽工程要求,由監(jiān)理單位組織各
有關人員進行中間驗收。
7.1.9采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)中間驗
收時,應符合下列規(guī)定:
1預制裝配干式地暖模塊的厚度、材料的性能指標,
同一廠家、同一產(chǎn)品抽檢次數(shù)不應少于2次,且地暖模塊鋪設
應符合設計要求;
2加熱管的材料、規(guī)格及敷設間距、彎曲半徑、固定
措施等應符合設計要求;
3供暖地面構造按要求設置;
4伸縮縫應按設計要求敷設完畢;
5加熱管管路與分水器、集水器的連接處在試驗壓力下
無滲漏;
6地面面層范圍內(nèi)加熱管不應有接頭,彎曲部分不得出
現(xiàn)硬折彎現(xiàn)象;
7閥門啟閉靈活,關閉嚴密;
8找平層、面層平整,表面無明顯裂縫。
7.1.10采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)檢驗
批劃分應符合下列規(guī)定
1檢驗批可按施工段或變形縫劃分;
2高層建筑標準層可按每3層(不足3層按3層計)
劃分檢驗批。
3不同構造做法的建筑地面工程應單獨劃分檢驗批。
4檢驗批的劃分也可根據(jù)方便施工與驗收的原則,由
23
施工單位與監(jiān)理(建設)單位共同商定。
7.1.11檢驗批質(zhì)量驗收合格,應符合下列規(guī)定:
1檢驗批應按主控項目和一般項目驗收;
2主控項目應全部合格;
3一般項目應合格;當采用計數(shù)檢驗時,至少應有90%
的檢查點合格,且其余檢查點不得有嚴重缺陷。
4應具有完整的施工方案和質(zhì)量檢查記錄。
7.2主控項目
7.2.1用于裝配式3D地暖模塊建筑地面工程的材料、其品
種規(guī)格應符合設計要求和現(xiàn)行有關標準的規(guī)定。
檢驗方法:觀察、尺量或稱重檢查、核查質(zhì)量證明文件。
檢查數(shù)量:按進場批次,每批隨機抽取三個試樣進行檢
查,質(zhì)量證明文件應按檢驗批進行核查。
7.2.2采用裝配式3D地暖模塊的分戶樓板撞擊聲隔聲性能
應符合設計要求和現(xiàn)行有關標準的規(guī)定。
檢驗方法:核查質(zhì)量證明文件、有效期內(nèi)的系統(tǒng)型式檢
驗報告。
檢查數(shù)量:全數(shù)檢查。
7.2.3裝配式3D地暖模塊使用的保溫板,其表觀密度、導
熱系數(shù)、壓縮強度、燃燒性能等應符合設計要求。
檢驗方法:核查質(zhì)量證明文件及進場復驗報告。
檢查數(shù)量:全數(shù)檢查。
7.2.4采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)使用
24
前,進入施工現(xiàn)場時應對裝配式3D地暖模塊的單位面積質(zhì)
量、抗壓強度進行復驗。復驗應為見證取樣送檢。
檢驗方法:核查質(zhì)量證明文件,隨機抽樣送檢,檢查復
驗報告。
檢查數(shù)量:同一工程、同一材料、同一生產(chǎn)廠家、同一
型號、同一規(guī)格、同一批號復驗一組。
7.2.5采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)施工前
應按照設計和施工方案的要求對基層進行處理,處理后應符
合裝配式3D地暖模塊施工方案的要求。
檢驗方法:對照設計和施工方案觀察檢查;核查隱蔽工
程驗收記錄。
檢查數(shù)量:每個檢驗批按自然間(或標準間)檢驗,抽
檢數(shù)量應隨機檢驗且不少于3間;不足3間,應全數(shù)檢查。
7.2.6采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)各層的
設置和構造做法以及各層的厚度應符合設計要求,并應按施
工方案進行施工。
檢查方法:對照設計和施工方案觀察檢查;尺量檢查。
檢查數(shù)量:每個檢驗批按自然間(或標準間)檢驗,抽
檢數(shù)量應隨機檢驗且不少于3間;不足3間,應全數(shù)檢查。
7.2.7穿越地面直接接觸室外空氣的各種管道應按設計要
求,采取隔斷聲、熱橋的保溫隔聲措施。
檢查方法:觀察;手扳檢查;保溫板厚度采用鋼針插入
或剖開尺量檢查;核查隱蔽工程驗收記錄。
檢查數(shù)量:每個檢驗批按自然間(或標準間)檢驗,抽
檢數(shù)量應隨機檢驗且不少于3間;不足3間,應全數(shù)檢查。
25
7.2.8有防水要求的地面,其裝配式3D地暖模塊做法不得
影響地面排水坡度,裝配式3D地暖模塊面層不得滲漏。
檢查方法:用長500mm的水平尺檢查;觀察檢查;
檢查數(shù)量:每檢驗批抽檢數(shù)量應按房間總數(shù)隨機檢驗且
不少于4間;不足4間,應全數(shù)檢查。
7.3一般項目
7.3.1裝配式3D地暖模塊系統(tǒng)所用材料的外觀和包裝應完
整無破損,符合設計要求和產(chǎn)品標準的規(guī)定。
檢驗方法:觀察檢查。
檢查數(shù)量:每個檢驗批按自然間(或標準間)檢驗,抽
檢數(shù)量應隨機檢驗且不少于3間;不足3間,應全數(shù)檢查。
7.3.2采用裝配式3D地暖模塊的地面輻射供暖系統(tǒng)的施工
應按照施工方案施工,裝配式3D地暖模塊應固定牢固,接
縫平整、嚴密。
檢驗方法:觀察、尺量。
檢查數(shù)量:每個檢驗批按自然間(或標準間)檢驗,抽
檢數(shù)量應隨機檢驗且不少于3間;不足3間,應全數(shù)檢查。
7.3.3裝配式3D地暖模塊安裝的允許偏差和檢查方法應符
合表7.3.3的規(guī)定。
表7.3.3裝配式3D地暖模塊安裝允許偏差和檢查方法
項目單位允許偏差檢查方法
表面平整度mm4.0用2m靠尺和楔形塞尺檢查
縫格平直mm3.0拉5m線和用鋼尺檢查
26
續(xù)表7.3.3
接縫高低差mm1.5用鋼尺和楔形塞尺檢查
踢腳線上口平直mm4.0拉5m線和用鋼尺檢查
板塊間隙寬度mm3.0用鋼尺檢查
27
附錄A抗沖擊性能試驗方法
裝配式3D地暖模塊系統(tǒng)抗沖擊性能
A1.1儀器準備
A1.1.1鋼球:高碳鉻軸承鋼鋼球,應符合GB/T308-2002的要
求,規(guī)格:公稱直徑63.5mm,質(zhì)量1045g。
A1.1.2抗沖擊儀:由落球裝置和帶有刻度尺的支架組成,分度
值0.01m。
A1.2試件制備
A1.2.1試驗用基材混凝土板性能應符合JC/T547-2017附錄
A的要求?;炷涟宄叽绮恍∮?00mm×800mm×(30~50)
mm,數(shù)量1塊。
A1.2.2隨機抽取1塊尺寸不小于400mm×600mm的保溫隔
聲輻射地暖模塊,預制溝槽三維支撐構造向上,用適當?shù)哪z
粘劑滿粘在基材混凝土板上,粘結厚度不小于5mm。
A1.2.3將制備的試伴置于環(huán)境溫度(23+2)℃,相對濕度
(50+5)%的標準條件下養(yǎng)護28d齡期。
A1.3試驗步驟
A1.3.1將試件預制溝槽三維支撐構造向上,水平放置在抗沖
擊儀的基底上,試件緊貼基底;
A1.3.2用鋼球在0.98m的高度上自由落體沖擊試件,沖擊5
處,沖擊點間距及沖擊點與試件邊緣的間距不得小于
100mm,試件表面沖擊點周圍出現(xiàn)破碎或脫落現(xiàn)象視為沖擊
點破壞。
28
A1.4結果評定
當5個沖擊點的破壞點小于2個時,判定合格。
29
本標準用詞說明
1為便于在執(zhí)行本標準條文時區(qū)別對待,對要求嚴格程度不
同的用詞說明如下:
1)表示很嚴格,非這樣做不可的:
正面詞采用“必須”;反面詞采用“嚴禁”;
2)表示嚴格,在正常情況下均應這樣做的:
正面詞采用“應”;反面詞采用“不應”或“不得”;
3)表示允許稍有選擇,在條件許可時首先應這樣做的:
正面詞采用“宜”;反面詞采用“不宜”;
4)表示有選擇,在一定條件下可以這樣做的,采用“可”。
2標準中指明應按其他有關標準、規(guī)范執(zhí)行時,寫法為:“應
按……執(zhí)行”或“應符合……的規(guī)定(或要求)”。
30
引用標準名錄
1《建筑材料放射性核素限量》GB6566
2《建筑材料及制品燃燒性能分級》GB8624
3《建筑地面設計規(guī)范》GB50037
4《民用建筑隔聲設計規(guī)范》GB50118
5《民用建筑熱工設計規(guī)范》GB50176
6《建筑地面工程施工質(zhì)量驗收規(guī)范》GB50209
7《建筑工程施工質(zhì)量驗收統(tǒng)一標準》GB50300
8《民用建筑工程室內(nèi)環(huán)境污染控制標準》GB50325
9《民用建筑設計統(tǒng)一標準》GB50352
10《建筑節(jié)能工程施工質(zhì)量驗收標準》GB50411
11《民用建筑供暖通風與空氣調(diào)節(jié)設計規(guī)范》GB50736
12《建筑節(jié)能與可再生能源利用通用規(guī)范》GB55015
13《建筑環(huán)境通用規(guī)范》GB55016
14《陶瓷磚試驗方法》GB/T3810
15《無機硬質(zhì)絕熱制品試驗方法》GB/T5486
16《泡沫塑料與橡膠線性尺寸的測定》GB/T6342
17《硬質(zhì)泡沫塑料壓縮性能的測定》GB/T8813
18《絕熱材料穩(wěn)態(tài)熱阻及有關特性的測定防護熱板法》
GB/T10294
19《采暖散熱器散熱量測定方法》GB/T13754
20《水泥膠砂強度檢驗方法(ISO法)》GB/T17671
21《冷熱水系統(tǒng)用熱塑性塑料管材和管件》GB/T18991
22《聲學建筑和建筑構件隔聲測量》GB/T19889
23《預拌砂漿》GB/T25181
31
24《預制溝槽保溫模塊地面輻射供暖系統(tǒng)應用技術規(guī)程》
CECS424
25《嚴寒和寒冷地區(qū)居住建筑節(jié)能設計標準》JGJ26
26《輕骨料混凝土技術規(guī)程》JGJ51
27《輻射供暖供冷技術規(guī)程》JGJ142
28《建筑砂漿基本性能試驗方法》JGJ/T70
29《預拌砂漿應用技術規(guī)程》JGJ/T223
30《耐堿玻璃纖維網(wǎng)格布》JC/T841
31《陶瓷磚膠粘劑》JC/T547
32《建筑絕熱用石墨改性擠塑聚苯乙烯泡沫板》JC/T2627
33《公共建筑節(jié)能設計標準》DB13(J)81
34《居住建筑節(jié)能設計標準(節(jié)能75%)》DB13(J)185
35《地面輻射供暖木質(zhì)地板鋪設技術和驗收規(guī)范》
WB/T1037
32
河北省工程建設標準
裝配式3D地暖模塊應用技術標準
T/HBZxxx一2023
條文說明
33
制定說明
《裝配式3D地暖模塊應用技術標準》T/HBZxxx一2023,經(jīng)
河北省墻材革新和建筑節(jié)能協(xié)會2023年xx月xx日以第xx號公
告批準發(fā)布。
為便于有關人員在使用本標準時能正確理解和執(zhí)行有關條文
規(guī)定,編制組按章、節(jié)、條順序編制了本標準的條文說明,對條
文規(guī)定的目的、依據(jù)以及執(zhí)行中需要注意的有關事項進行了說明。
但是,本條文說明不具備與標準正文同等的法律效力,僅供使用
者作為理解和把握條文規(guī)定的參考。
34
目次
1總則·······································································36
2術語·······································································37
3基本規(guī)定·····································
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
- 4. 未經(jīng)權益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責。
- 6. 下載文件中如有侵權或不適當內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 交通設備制造業(yè)數(shù)字化轉(zhuǎn)型與工業(yè)4.0融合發(fā)展報告
- 2025年網(wǎng)絡購物平臺專職導購員服務協(xié)議書
- 2025年度電商平臺物流配送預付款及結算服務合同
- 2025年度豬肉市場數(shù)據(jù)共享與金融服務合作協(xié)議
- 2025年航空航天涂層材料深度合作協(xié)議
- 湖州職業(yè)技術學院《土壤生態(tài)綜合實驗》2024-2025學年第一學期期末試卷
- 山東協(xié)和學院《環(huán)境水文地質(zhì)學》2024-2025學年第一學期期末試卷
- 武漢傳媒學院《老年社會工作實務》2024-2025學年第一學期期末試卷
- 大連醫(yī)科大學《信息化管理》2024-2025學年第一學期期末試卷
- 浙江音樂學院《工程材料》2024-2025學年第一學期期末試卷
- 疫情防控實戰(zhàn)演練方案腳本
- 資產(chǎn)評估事務所投標服務方案總體工作方案評估工作關鍵性內(nèi)容及重難點分析
- Q∕SY 1356-2010 風險評估規(guī)范
- 拆卸與安裝油箱加油管
- 《綠色物流與綠色供應鏈》PPT課件
- ISO13485-2016醫(yī)療器械質(zhì)量管理體系全套資料(手冊、程序文件、記錄表單)
- 術前訪視和術前準備注意事項.pptx
- 滬科版七年級數(shù)學上冊全套ppt課件
- SCH壁厚等級對照表
- 特種車輛維護保養(yǎng)技術協(xié)議
- 函數(shù)的單調(diào)性 (2)
評論
0/150
提交評論